NFT-1000
The NFT-1000 fuel temperature monitoring channel converts millivolt signals from thermocouples into a usable signal level for monitoring and display. It includes a dual trip unit, a calibrator module to test the channel trip functions as well as provide a fixed calibration point for verifying the correct operation of the unit, and an isolated transmitter module to drive external indicating-recording devices. The NFT-1000 is designed to be physically similar to the other modules in the line of analog instrumentation modules.
NFT-1000 FUEL TEMPERATURE MONITORING SPECIFICATIONS | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|
INPUT RANGE | 0 to 1000° C (Type K Thermocouple), 3 Independent Channels | |||||||||
OUTPUTS | Isolated | 0-10 V or 4-20 mA for Each Channel | ||||||||
BISTABLE TRIPS | Temp A Trip 1 Temp A Trip 2 Temp B Trip 1 Temp B Trip 2 Temp C Trip 1 Temp C Trip 2 | Adjustable, 2 Form C Contacts Adjustable, 2 Form C Contacts Adjustable, 2 Form C Contacts Adjustable, 2 Form C Contacts Adjustable, 2 Form C Contacts Adjustable, 2 Form C Contacts | ||||||||
LINEARITY | ±1% of Full Scale | |||||||||
TEMPERATURE COEFFICIENT | ±0.04%/°C Maximum in the Range of 10° to 50°C | |||||||||
POWER | 117 Vac ± 10%, 50/60 Hz @ 1.0 Amp | |||||||||
DIMENSIONS (Approximate) | Maximum 4.6 inches (W) x 8.3 inches (H) x 15.8 inches (D) (16.7 (D) with connectors and front panel potentiometer) | |||||||||
WEIGHT (Approximate) | 11 pounds |